dc.description.abstract |
In this paper, based on the theory of traveling waves, the fault distances on long transmission lines with various series-compensation levels are determined using transient current and voltage frequencies. Transmission lines with series compensation are modeled using Alternative Transients Program software with frequency-dependent effects on the line included in the simulation. The transient current and voltage signals are obtained from the model. A fast Fourier transform is used for frequency-domain conversion and fault location is estimated from the frequencies of fault-generated harmonics in the transient spectrum. The algorithm is implemented in MATLAB. To investigate the effect of compensation on accuracy, the results are obtained for different series-compensation levels. The undesirable source-inductance effect is removed and estimation accuracy is further improved using a waveform-relaxation method. The method is found to be successful in determining fault location on series-compensated transmission lines. The effects of the compensation level, fault resistance, and phase angle are investigated. |
tr_TR |
dc.language.iso |
eng |
tr_TR |
dc.publisher |
Tubıtak scıentıfıc & technıcal research councıl turkey, ataturk bulvarı no 221, kavaklıdere, ankara, 00000, turkey |
tr_TR |
dc.relation.isversionof |
10.3906/elk-1606-180 |
tr_TR |
dc.rights |
info:eu-repo/semantics/openAccess |
tr_TR |
dc.subject |
Algorıthm |
tr_TR |
dc.subject |
spectrum |
tr_TR |
dc.title |
Fault location determination for transmission lines with different series-compensation levels using transient frequencies |
tr_TR |
dc.type |
article |
tr_TR |
dc.relation.journal |
Turkısh journal of electrıcal engıneerıng and computer scıences |
tr_TR |
dc.contributor.department |
İnönü Üniversitesi |
tr_TR |
dc.identifier.volume |
25 |
tr_TR |
dc.identifier.issue |
5 |
tr_TR |
dc.identifier.startpage |
3764 |
tr_TR |
dc.identifier.endpage |
3775 |
tr_TR |