DSpace@İnönü

Fault location determination for transmission lines with different series-compensation levels using transient frequencies

Basit öğe kaydını göster

dc.contributor.author Akmaz, Duzgun
dc.contributor.author Mamis, Mehmet Salih
dc.contributor.author Arkan, Muslum
dc.contributor.author Tagluk, Mehmet Emin
dc.date.accessioned 2019-08-09T09:29:07Z
dc.date.available 2019-08-09T09:29:07Z
dc.date.issued 2017
dc.identifier.citation Akmaz, D . Mamis, MS. Arkan, M. Tagluk, ME. (2017). Fault location determination for transmission lines with different series-compensation levels using transient frequencies.Cilt:25. Sayı:5. 3764- 3775 ss. tr_TR
dc.identifier.uri http://hdl.handle.net/11616/13359
dc.description.abstract In this paper, based on the theory of traveling waves, the fault distances on long transmission lines with various series-compensation levels are determined using transient current and voltage frequencies. Transmission lines with series compensation are modeled using Alternative Transients Program software with frequency-dependent effects on the line included in the simulation. The transient current and voltage signals are obtained from the model. A fast Fourier transform is used for frequency-domain conversion and fault location is estimated from the frequencies of fault-generated harmonics in the transient spectrum. The algorithm is implemented in MATLAB. To investigate the effect of compensation on accuracy, the results are obtained for different series-compensation levels. The undesirable source-inductance effect is removed and estimation accuracy is further improved using a waveform-relaxation method. The method is found to be successful in determining fault location on series-compensated transmission lines. The effects of the compensation level, fault resistance, and phase angle are investigated. tr_TR
dc.language.iso eng tr_TR
dc.publisher Tubıtak scıentıfıc & technıcal research councıl turkey, ataturk bulvarı no 221, kavaklıdere, ankara, 00000, turkey tr_TR
dc.relation.isversionof 10.3906/elk-1606-180 tr_TR
dc.rights info:eu-repo/semantics/openAccess tr_TR
dc.subject Algorıthm tr_TR
dc.subject spectrum tr_TR
dc.title Fault location determination for transmission lines with different series-compensation levels using transient frequencies tr_TR
dc.type article tr_TR
dc.relation.journal Turkısh journal of electrıcal engıneerıng and computer scıences tr_TR
dc.contributor.department İnönü Üniversitesi tr_TR
dc.identifier.volume 25 tr_TR
dc.identifier.issue 5 tr_TR
dc.identifier.startpage 3764 tr_TR
dc.identifier.endpage 3775 tr_TR


Bu öğenin dosyaları:

Bu öğe aşağıdaki koleksiyon(lar)da görünmektedir.

Basit öğe kaydını göster