Robust temperature control of MSF desalination plants with coefficient diagram method

Küçük Resim Yok

Tarih

2003

Dergi Başlığı

Dergi ISSN

Cilt Başlığı

Yayıncı

Erişim Hakkı

info:eu-repo/semantics/closedAccess

Özet

Design of a controller sufficiently robust to the parametric uncertainties for the plant parameters is an important problem. Coefficient Diagram Method (CDM) is shown to be an efficient control technique to solve this problem. The controller design by CDM is based on the choice of the coefficients of the characteristic polynomial of the closed loop system according to the convenient performance criteria such as equivalent time constant, and stability indices. In this study, the controllers are designed for three temperature loops of large Multi-stage flash (MSF) desalination system by using CDM; then, obtained time domain characteristics are compared with the results of some other methods. It is shown that CDM design is more stable and robust whilst giving the desired time domain system performance.

Açıklama

Proceedings of 2003 IEEE Conference on Control Applications -- 23 June 2003 through 25 June 2003 -- Istanbul -- 61822

Anahtar Kelimeler

Coefficient diagram method, MSF desalination plants, Robustness