A new Smith predictor and controller for control of processes with long dead time

Küçük Resim Yok

Tarih

2003

Yazarlar

Dergi Başlığı

Dergi ISSN

Cilt Başlığı

Yayıncı

Elsevier Science Inc

Erişim Hakkı

info:eu-repo/semantics/closedAccess

Özet

Good control of processes. With long dead time is often achieved using a Smith predictor configuration. Typically a PI or PID controller is used; however, it is shown in this paper that for some situations improved set point and disturbance responses can be obtained if a PI-PD controller is Used. Several methods are possible for selecting the parameters of the PI-PD controller but when the plant transfer function has no zeros, the use of the standard forms provides a simple algebraic approach, and also reveals why difficulties may be encountered if a PID controller is used. Some examples are given to show the value of the approach presented. (C) 2003 ISA-The Instrumentation, Systems, and Automation. Society.

Açıklama

Anahtar Kelimeler

predictive control, integral performance indices, delay compensation, PID controllers, disturbance rejection

Kaynak

Isa Transactions

WoS Q Değeri

Q3

Scopus Q Değeri

Q1

Cilt

42

Sayı

1