Design and development of travelling-wave-frequency-based transmission line fault locator using TMS320 DSP
Küçük Resim Yok
Tarih
2019
Dergi Başlığı
Dergi ISSN
Cilt Başlığı
Yayıncı
Inst Engineering Technology-Iet
Erişim Hakkı
info:eu-repo/semantics/closedAccess
Özet
The authors use a TMS320 digital signal processor (TMS320-DSP) to determine fault instants and estimate their location in real time in a laboratory environment. The fault instant is determined via examining the instantaneous differential changes in the line currents. After the fault is detected, the fault location is determined by processing the time-domain transient current waves. First, the travelling-wave frequency is determined by application of the fast Fourier transform to the positive-sequence-component line current after the fault, and subsequently, the fault location is estimated by utilising this frequency. The alternative transients programme (ATP)-electromagnetic transient programme is used to simulate the line currents and create short-circuit fault conditions. Furthermore, LabVIEW software and a National Instruments data acquisition board are used to transform the line currents obtained through the ATP programme into analogue signals. The TMS320-DSP determines the fault in real time and estimates the fault location using the completed software and analogue input signals. Their results indicate that the prototype device designed with the use of the TMS320-DSP is suitable for real-time fault detection.
Açıklama
Anahtar Kelimeler
EMTP, power system transients, power distribution faults, power transmission lines, power transmission faults, data acquisition, fault diagnosis, fast Fourier transforms, digital signal processing chips, signal processing, fault location, virtual instrumentation, fault location, time-domain transient current waves, travelling-wave frequency, positive-sequence-component line, alternative transients programme-electromagnetic transient programme, line currents, short-circuit fault conditions, TMS320-DSP, real-time fault detection, travelling-wave-frequency-based transmission line fault locator, TMS320 digital signal processor, fault instant
Kaynak
Iet Science Measurement & Technology
WoS Q Değeri
Q3
Scopus Q Değeri
Q2
Cilt
13
Sayı
4